The Transformer on load
It has been shown that a primary input voltage can be transformed to any desired open-circuit secondary voltage by a suitable choice of turns ratio. is available for circulating a load current impedance. For the moment, a lagging power factor will be considered. The secondary current and the resulting ampere-turns will change the flux, tending to demagnetize the core, reduce and with it . Because the primary leakage impedance drop is so low, a small alteration to will cause an appreciable increase of primary current from to a new value of equal to . The extra primary current and ampere-turns nearly cancel the whole of the secondary ampere-turns. This being so , the mutual flux suffers only a slight modification and requires practically the same net ampere-turns as on no load. The total primary ampere-turns are increased by an amount necessary to neutralize the same amount of secondary ampere-turns. In the vector equation , ; alternatively, . At full load, the current is only about 5% of the full-load current and so is nearly equal to. Because in mind that , the input kVA which is approximately is also approximately equal to the output kVA, .